What Size Generator Do I Need for a Well Pump?

Portable generator in a snowy yard far from the house, cord running to a wellhouse

Franklin Electric, a major submersible-motor maker, lists these minimum generator sizes for single-phase well-pump motors: 2 kW for 1/2 HP, 3 kW for 3/4 HP, 4 kW for 1 HP and 5 kW for 1.5 HP. 2-wire motors need 50% more. Those are minimums for an externally regulated generator running the pump alone. Add everything else you want powered on top (Franklin Electric AIM Manual, Table 3).

A pump that draws under 1,000 W while running can need several times that for the split second it starts. That is why “just add up the running watts” undersizes well-pump generators.

Minimum generator size by pump horsepower

Motor HPFranklin minimum (kW)Minimum (kVA)2-wire motor (+50%)
1/31.5 kW1.9 kVA2.25 kW
1/22 kW2.5 kVA3 kW
3/43 kW3.8 kVA4.5 kW
14 kW5.0 kVA6 kW
1.55 kW6.25 kVA7.5 kW
27.5 kW9.4 kVA—
310 kW12.5 kVA—
515 kW18.75 kVA—

Source: Franklin Electric AIM Manual, Table 3 (minimum rating, externally regulated). The 2-wire column is our calculation from Franklin’s note that 2-wire motors need a rating 50% higher. Franklin’s 4-inch 2-wire motors in Table 29 stop at 1.5 HP, hence the dashes. Franklin also says to follow the generator maker’s de-rating for high elevation or natural gas.

How to size the generator, step by step

  1. Find the pump’s HP, voltage and wire type on the motor nameplate or the control box near the pressure tank. A separate control box means 3-wire.
  2. Look up the Franklin minimum in the table above, and add 50% if it is a 2-wire motor.
  3. Check the voltage. A 230V pump needs a generator with a 120/240V outlet (such as an L14-30R or 14-50R). A 120V-only inverter generator can’t run it.
  4. Add your other running loads (refrigerator, furnace blower, lights) with the sizing calculator or our whole-house generator guide.
  5. De-rate for elevation or natural-gas/propane operation per the generator maker. Dual-fuel models list lower watts on propane.
  6. Plan a transfer switch. Franklin states that automatic or manual transfer switches must be used any time a generator is used as standby or backup on power lines.
  7. Start the generator before the pump, and shut off the pump before the generator. Franklin warns the motor thrust bearing can be damaged if the generator coasts down or runs out of fuel with the motor running.

⚠️ Panel, transfer switch, and interlock work: hire a licensed electrician

Installing a transfer switch, a generator interlock kit, a power inlet box, or any connection to your home’s electrical panel is a job for a licensed electrician, and most areas require a permit and inspection. Never backfeed a generator or power station through a wall outlet: it can energize utility lines and electrocute line workers. Power Outage Planner is not an electrical contractor, and this page is general information, not installation advice.

Rules from the motor maker that people miss

  • Voltage during start-up: the generator must deliver at least 65% of the motor’s nameplate voltage while starting.
  • No reduced-voltage starter on a minimum-size generator. Both drop voltage, and Franklin warns the combination can cause severe motor damage.
  • Frequency matters: a pump running 1–2 Hz below nameplate won’t meet its performance curve, and 1–2 Hz above may trip overloads.
  • Externally vs internally regulated: Table 3 is for externally regulated generators, which Franklin says most are.

Generator classes that fit common well pumps

PumpFranklin minimumExample generators (maker spec, gasoline)
1/2 HP 3-wire2 kWAny 120/240V generator rated at least 2 kW running (a 120V-only inverter can’t run a 230V pump)
1/2 HP 2-wire or 3/4 HP 3-wire3 kWGenerac GP8000E (8,000 running / 10,000 starting W, 120/240V 30A)
1 HP 2-wire6 kWChampion 9375W Dual Fuel (7,500 running W), Generac GP8000E
1.5 HP 2-wire, plus house loads7.5 kW + loadsWestinghouse 12500W Dual Fuel (9,500 running W, L14-30R and 14-50R)

Specs are from each maker’s official Amazon listing, checked November 3, 2026. Running watts on propane are lower. For example, Westinghouse lists 8,500 running W on propane. Read the generator manual for the outlet that matches your transfer switch.

Generators sized for a well pump, live prices

Generac GP8000E

Black Friday Deal

Generac GP8000E

10,000 starting / 8,000 running W, 120/240V 30A, COsense

$1,124.00Check price on Amazon →

List price $1,299.00, 13% off (Amazon)

Champion 9375W Dual Fuel

Champion 9375W Dual Fuel

9,375 starting / 7,500 running W on gasoline, CO Shield

$874.99Check price on Amazon →

Westinghouse 12500W Dual Fuel

Westinghouse 12500W Dual Fuel

12,500 peak / 9,500 running W (gas), 120/240V 14-50R

$999.00Check price on Amazon →

As an Amazon Associate we earn from qualifying purchases. Amazon prices as of Nov 27, 6:34 PM ET. Prices and deals change often; the price on Amazon at checkout applies.

⚠️ Carbon monoxide: run fuel-burning equipment outdoors only

Generators, grills, camp stoves, and other gasoline-, propane-, or charcoal-burning devices give off carbon monoxide, an odorless, colorless gas that can kill within minutes. Never use them inside your home, garage, carport, or basement, or near doors, windows, or vents, even with doors and windows open. Keep a portable generator outdoors at least 20 feet from the house with the exhaust pointed away, and install battery-operated or battery-backup CO alarms. If an alarm sounds or anyone feels dizzy, weak, or sick, get to fresh air right away and call 911. Read our carbon monoxide safety guide (based on CDC and U.S. CPSC guidance).

A generator can kill without the right setup. Put a battery CO alarm on every level of the house before you run one. Ready.gov says to keep generators outdoors and at least 20 feet from windows, doors and attached garages (Ready.gov, Winter Weather).

Battery CO alarms, live prices

First Alert CO710

First Alert CO710

10-year battery CO alarm with digital display

$44.49Check price on Amazon →

Kidde CO alarm

Deal selling fast

Kidde CO alarm

AA battery CO alarm, works in an outage

$21.22Check price on Amazon →

First Alert CO400

First Alert CO400

Battery-powered CO alarm

$21.99Check price on Amazon →

As an Amazon Associate we earn from qualifying purchases. Amazon prices as of Nov 27, 6:34 PM ET. Prices and deals change often; the price on Amazon at checkout applies.

Prefer a quiet, fuel-free option?

For 1/2–3/4 HP pumps, a large power station with 240V output can do the job. See best power station for a well pump and generator or power station.

Frequently asked questions

What size generator do I need for a 1/2 HP well pump?

Franklin Electric lists a 2 kW minimum (2.5 kVA) for a 1/2 HP motor on an externally regulated generator, and 50% more, 3 kW, for a 2-wire motor. That covers the pump only. Add your other loads on top.

What size generator do I need for a 1 HP well pump?

Franklin’s minimum is 4 kW (5.0 kVA) for a 1 HP motor, or 6 kW if it is a 2-wire motor. Make sure the generator has 120/240V output if the pump is 230V.

Can an inverter generator run a well pump?

Only if its rating meets the Franklin minimum and it supplies the pump’s voltage. Many small inverter generators are 120V only, so they can’t run a 230V pump. Check the generator’s outlets and surge rating against the table.

Do I need a transfer switch to run my well pump on a generator?

Franklin Electric states that automatic or manual transfer switches must be used any time a generator is used as standby or backup on power lines. It is also what prevents dangerous backfeed. Have a licensed electrician install it.

Why does my well pump trip the generator?

Usually the generator is too small for the start-up demand, the pump is 2-wire (which needs 50% more), or other loads are running when the pump starts. Franklin also warns against pairing a reduced-voltage starter with a minimum-size generator.